• +976-70008383
  • info@energytech.mn
Choice language :
PV3, PV4

Single-core wires with PVC insulation for electric facilities per GOST 6323- 79
PV-З is wire wuth Cu core and insulation from PVC compound, characterized by high flexible

PV-4 is wire wuth Cu core and insulation from PVC compound, characterized by highest flexible

 

CONSTRUCTION

  1. CONDUCTING CORE:
    — PV-3 wires: Cu, multi-cores, class 2, 3 or 4 for cross-section from 0,5 up to 1.5 mm2 incl., class 4 for cross-section from 2.5 up to 4 mm2 incl., class 3 for cross-section from 6 up to 95 mm2 incl. per GOST 22483;
    — PV-4wires: multi-cores, class 5 for cross-section from 0,5 and 0.75 mm2, class 4 or 5 for crosssection from 1 and 1.5 mm2, class 5 for cross-section from 2.5 and 4 mm2, class А or 5 for crosssection from 6 and 10 mm2 per GOST 22483. 
  2. INSULATION: from PVC compound various coloring. Coloring is continuous or of 2 longitudinal stripes put diametrically on insulation of natural color. The wires, used as grounding core have greenyellow coloring. The color of solid insulation or stripes should be bespeaced at ordering and have identification mark,

APPLICATION
Wires are apply for electric facilities at stationary cabling in lighting and power networks, and also for installation of electric equipment, machines and devices on nominal AC voltage up to 450 V (from networks up to 450/750 V) of frequency up to 400 Hz or DC voltage up to 1 kV.
PV-З apply for installation of electric networks, where the wire’s bendings are possible.
PV-4 apply for installation of electric networks, where the often wire’s bendings are possible.


OKP CODES:
35 5113 03 — for PV-З wires
35 5113 21 — for PV-4 wires


TECHNICAL SPECIFICATION
Climatizaton type “HL”, allocation category 2 per GOSTТ 15150-69.
Wires are resistant to action of environment temperature...............................from -500С up to +700С
Wires are resistant to action ofair relative humidity 100% at temperature +350С
Wires are resistant to action of mold fungi.
Wires are resistant to action of mechanical shocks, linear acceleration, bendings, vibration strains, audio noises.
Wires are not spread the burning.
Installation of wire at temperature not lower than ........................................-150С
Bending radius at cabling, not less ...............................................................5 diameters of the wire
Permissible cpntinuous heating of the cores, not more than ...........................+700С
Construction lengh, not less than ...............................................................100 m

 

PV-3
Number of cores
and the cross section, mm2
Outer
cable diameter
Weight of 1 km of cable, kg
1х0,5
2,10
8,2
1х0,75
2,30
10,3
1х1
2,50
13,6
1х1,5
3,00
20,2
1х2,5
3,70
32,2
1х4
4,20
46,5
1х6
4,70
66,9
1х10
6,30
111,6
1х16
7,50
173,9
1х25
9,20
266,9
1х35
10,30
349,0
1х50
12,30
497,7
1х70
14,40
681,0
1х95
16,30
923,1
1х120
18,20
1180,5
1х150
20,00
1430,7
1х185
22,20
1767,0
1х240
25,50
2346,6

 

 
 

 

PV-4
Number of cores
and the cross section, mm2
Outer
cable diameter
Weight of 1 km of cable, kg
1х0,5
2,00
8,1
1х0,75
2,30
10,7
1х1
2,50
13,6
1х1,5
3,00
20,2
1х2,5
3,50
30,4
1х4
4,20
46,5
1х6
4,70
66,9
1х10
6,30
111,6
1х16
7,50
173,9
1х25
9,20
266,9
1х35
10,30
349,0
1х50
12,30
497,7
1х70
14,10
681,0
1х95
16,30
923,1
1х120
18,20
1180,5
1х150
20,00
1430,7
1х185
22,20
1767,0
1х240
25,50
2326,6